Quick Guide Firmware Update Monitoring System 50/ 100 II/ 100 III/ 500 II

This firmware update is intended exclusively for the latest generation of Didactum`s monitoring devices.

  • Didactum Monitoring System 50
  • Didactum PDU 700
  • Didactum Monitoring System 100 II
  • Didactum PDU 750
  • Didactum Monitoring System 100 III
  • Didactum Monitoring System 700
  • Didactum Monitoring System 500 II

The first generation of Didactum`s monitoring units (100/400/500/500DC/600) does not support this kind of firmware update procedure!

Important:

Please ensure that you save the configuration of your network-enabled monitoring system as well as the syslog and the sensor data before updating. This firmware will restore the device to factory delivery state! Please follow the instructions very carefully. If you have any questions, please contact the support via e-mail to support@didactum.com

The firmware update of the Didactum monitoring device can be done in two ways

  • Firmware Update Tool
  • Firmware update via the web interface (from installed firmware version "2.7.1.-b1762" or later)

Please use the firmware update tool (1), if an earlier firmware than the release "2.7.1.-b1762" is installed. With the help of this tool, your monitoring unit is reset to the factory-delivery state. The firmware update via the Web Interface (2) is used to update the unit directly via the WebGUI. Please note that the firmware version "2.7.1.-b1762" (or higher) must be installed on the monitoring system.

Installation of USB drivers for Windows Operating Systems

Please unpack the “ WinUSB.zip” file. This file contains an .exe file ( "WinUSB4NuVCOM_NUC970.exe") with the necessary USB drivers for your monitoring
unit. If necessary, you must enter the admin password of your Windows OS for the driver installation.

After a successful driver installation, you will find a new device driver called "NuVCOMDeviceClass" in the Windows system control under Device manager.

Please restart your Windows computer after sucessful driver installation.

Installation of firmware update tool

Please unpack the packed "Writer.zip" file. In the packed folder you will find the tool called "NuWriter.exe". Please start this tool.

If necessary, you must enter the admin password for your OS. Please disconnect your monitoring device from the power supply (12). Use a ballpoint pen to change the DIP switch (8) to position „Recovery". Then reconnect the power supply. Connect the device to your computer using a USB mini cable. The „NuWriter" tool will then indicate the processor type of your monitoring unit automatically. Please check if "NUC976DK62Y.ini" has been detected successfully.

Caution:

Please check if the type “SPI”is recognized correctly. "DDR Init" must be set to "NUC976DK62Y.ini". If the USB cable is not already connected to the monitoring unit, please plug it in and click on "Re-Connect". Under "Parameters", select the firmware file called "didactum-2.7.1-xxx.bin". Do not choose the file with suffix “zor”. “Pack” must be chosen as “ImageType”.

Firmware installation

Download the appropriate firmware release for your monitoring device from here.

After unpacking the zip file, you will find a file with the suffix ".zor", such as eg "didactum-2.7.1-b1991.zor". This firmware file can be easily installed via the web interface of your IT monitoring system.

Depending on the size of the update, the firmware update procedure can take several minutes. Please do not interrupt the power supply and network connection during the update! After the successful update, the new firmware version is displayed under "System menu".

Contrary to expectations, if the firmware update should fail, please repeat the process. In very rare cases, you must install the firmware with the firmware update tool. Then follow the instructions described in point 1.

After succesful firmware update

After succesful firmware update, please disconnect 50/100 II/100 III/500 II remote monitoring appliances from power supply. Use the ballpoint pen again to change the DIP switch from „Recovery" to „Normal“ mode. 

Then reconnect the remote monitoring device to the power supply and connect the network cable.

Your remote monitoring unit has been restored to the original factory settings with the default IP address "192.168.0.193“.

Important:

Please remember that the "Guest" account of your monitoring device has all access rights / admin rights!

Please log in as "guest" (without quotes) and configure the users and their rights.

The user name is: guest
The password / login is: guest

Please also note the FAQs. Here we give answera to the most frequently asked questions. If you have any further questions, please contact Didactum`s support by e-mail: support(at)didactum.com

Please provide our support team with the following information:

  • Exact information about your problem, including details of your system environment
  • Product name(s) including serial number(s)
  • Installed firmware version of your Didactum Monitoring System